Application coordination, Application coordination -5, Figure 4-7. coordination timing diagram – Basler Electric BE1-50/51B-244 User Manual

Page 33

Advertising
background image

9252000793 Rev C

BE1-50/51B-244 Installation

4-5

Application Coordination

In a typical application coordination scheme, a BE1-50/51B-244 is used to provide primary protection for a

radial distribution feeder. An electromechanical overcurrent relay with extremely inverse timing provides

protection for the transformer and bus. To improve coordination with the electromechanical relay, the

BE1-50/51B-244 is configured with the following settings:

Integrating reset enabled (SW3-4 ON)

Westinghouse CO type curves selected (SW3-3 OFF)

The feeder reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a

permanent fault occurs (magnitude 10 times pickup), calculate the feeder breaker trip time for each of the

three operations. Refer to Appendix A for the characteristic curve constants and definition of the terms

used in the following time characteristic curve equations.
From the time characteristic curve equation:

K

BD

C

M

AD

T

N

T

+

+

=

028

.

0

)

2

02758

.

0

(

1

10

2

7624

.

7

0938

.

2

+

×

+

×

=

= 0.209 seconds

From the reset characteristic curve equation:

1

M

RD

T

2

R

=

M equals 0 if current goes to zero. A negative result indicates reset time.

seconds

15.5

1

0

2

7.75

2

=

×

=

Result: Full trip = 0.209 seconds and full reset = 15.5 seconds if current goes to zero.

In Figure 4-7:
T

A

= 0.209 seconds (relay was at reset)

T

B

= value<T

A

because rewind has not gone to zero

T

C

= value<T

A

because rewind has not gone to zero

Figure 4-7. Coordination Timing Diagram

Advertising