Basler Electric BE1-50/51B-219 User Manual

Page 16

Advertising
background image

10

9252000981 Rev J

From the time characteristic curve equation:

K

BD

C

M

AD

T

N

Trip

+

+

=

(

)

028

0

2

02758

.

0

1

10

2

7624

7

0938

2

.

.

.

+

×

+

×

=

028

0

05516

.

0

1

10806

124

5248

15

.

.

.

+

+

=

seconds

0.209

=

From the reset characteristic curve equation:

1

M

RD

T

2

Reset

=

seconds

15.5

1

0

2

7.75

2

=

×

=

M = 0 if current goes to zero.

Negative result indicates reset time.

Results: Full trip = 0.209 seconds and full reset = 15.5 seconds if current goes to zero.

In Figure 4,

T

A

= 0.209 seconds (relay was at reset).

T

B

= value < T

A

because rewind has not gone to zero.

T

C

= value < T

A

because rewind has not gone to zero.

Figure 4. Coordination Timing Diagram

Installation

BE1-50/51B-219/-226

Advertising