Type tests, Isolation, Surge withstand capability – Basler Electric BE1-50/51B-219 User Manual

Page 34: Radio frequency interference (rfi), Vibration, Shock, Environment, Agency recognition, Gost-r certification, Physical

Advertising
background image

28

9252000981 Rev J

Type Tests

Isolation

Meets IEC 255-5 and exceeds IEEE C37.90-2005, one-minute dielectric (high potential) tests as follows.
All circuits to ground:

2,828 Vdc or 2,000 Vac

Input to Output Circuits:

2,828 Vdc or 2,000 Vac

Surge Withstand Capability

Qualified to IEEE C37.90.1-2002 Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems.

Impulse

Qualified to IEC 255-5.

Radio Frequency Interference (RFI)

Qualified to IEEE C37.90.2-2004.

Field-tested using a 5-watt, hand-held transceiver operating at random frequencies centered around 144
MHz and 440 MHz, with the antenna located 6 inches from the relay in both horizontal and vertical
planes.

Vibration

Withstands 2 G in each of three mutually perpendicular planes swept over the range of 10 to 500 Hz for a
total of 6 sweeps, 15 minutes each sweep.

Shock

Withstands 15 G in each of three mutually perpendicular planes.

Environment

Operating Temperature:

–40

°C to 70°C (–40°F to158°F)

Storage Temperature:

–50

°C to 70°C (–58°F to 158°F).

Agency Recognition

GOST-R Certification

GOST-R certified per the relevant standards of Gosstandart of Russia.

Physical

Weight:

6.1 lb (2.77 kg)

Specifications

BE1-50/51B-219/-226

Advertising