BE1-50/51B-219 and BE1-50/51B-226 electrical and physical specifications are listed in the following
paragraphs.

Current Sensing Input

BE1-50/51B-219

Continuous Current:

14 Aac

One-Second Rating:

400 Aac

BE1-50/51B-226

Continuous Current:

2.8 Aac

One-Second Rating:

80 Aac

Time Overcurrent (51) Element

Setting the TIME PICKUP control at the minimum pickup setting places the relay in the most sensitive
state and may be used as a safety setting.

BE1-50/51B-219 Pickup

Setting Range:

0.5 to 15.9 Aac

Setting Increment:

0.1 Aac

Accuracy:

±2%, ±25 milliamperes at or above 0.5 ampere setting

BE1-50/51B-226 Pickup

Setting Range:

0.1 to 3.18 Aac

Setting Increment:

0.02 Aac

Accuracy:

±2%, ±5 milliamperes at or above 0.1 ampere setting

Dropout

Dropout occurs at 95% of pickup value.

Timing Range

0.0 to 9.9 seconds in 0.1 second steps.

Timing Accuracy

The timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times
tap and is for a given measured multiple of tap. The measurement of the multiple of tap has an accuracy
that is the sum of ±2%, ±25 milliamperes for the BE1-50/51B-219 and ±2%, ±5 milliamperes for the BE1-
50/51B-226.

Timing Accuracy Example (BE1-50/51B-219)

PU setting:

5 amperes

Current Applied:

6.5 amperes

+ Multiple Tolerance:

6.655 amperes

– Multiple Tolerance:

6.345 amperes

Time Curve:

E

Time Dial:

5.0

Minimum time dial
using 6.655 amperes:

46.5470 seconds

BE1-50/51B-219/-226

Specifications