Introduction, Features – Basler Electric BE1-50/51B-219 User Manual

Page 7

Advertising
background image

9252000981 Rev J

1

Introduction

BE1-50/51B-219 and BE1-50/51B-226 protective relays are direct replacements for Westinghouse/ABB
type CO relays. The BE1-50/51B-219 has a 5-ampere current sensing input. The BE1-50/51B-226 has a
1-ampere current sensing input. Specific relays by catalog number are listed in Table 1.

Table 1. ABB Relays Suitable for Direct Replacement

ABB Catalog Number

Curve Type

CO-2

∗11∗1N

Short Time

CO-5

∗11∗1N

Long Time

CO-6

∗11∗1N

Definite

CO-7

∗11∗1N

Moderately Inverse

CO-8

∗11∗1N

Inverse

CO-9

∗11∗1N

Very Inverse

CO-11

∗11∗1N

Extremely Inverse

∗ Any digit covering all pickup ranges and 50 Hz or 60 Hz models.

To replace an existing Westinghouse/ABB type CO (hereinafter referred to as ABB relay), perform the
following steps:

1.

Select the desired relay settings on your new BE1-50/51B-219 or BE1-50/51B-226 relay.

2.

Remove the existing ABB relay cradle.

3.

Insert the new relay cradle.

4.

Close the knife-blade switches.

5.

Install the new Basler Electric cover and secure with the captive thumbnut.

Basler Electric BE1-50/51B-219 and BE1-50/51B-226 protective relays are self-powered, microprocessor-
based, non-directional phase or ground relays that monitor the magnitude of a single-phase ac current to
provide accurate instantaneous and time overcurrent protection for 50- or 60-hertz power systems. Each
model covers 15 popular time characteristics, a wide range of pickup settings, and field-selectable
instantaneous or integrating reset.

Features

A wide range of pickup settings and front-panel-selectable time characteristics permit applications
involving coordination with fuses, reclosers, cold-load pickup, motor starting, and fixed-time requirements.
Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.

BE1-50/51B-219 and BE1-50/51B-226 overcurrent relays have the following standard features:

Independent time and instantaneous elements

A secure method to manually trip the breaker at the relay front panel

Direct reading front-panel controls

Minimum pickup setting for safety during installation

Time characteristics extend to a pickup multiple of 40

Rugged draw-out construction with steel case

Gravity-latching targets retain indication without power

Built-in accuracy eliminates internal adjustments

Minimum transient overreach

Field-selectable characteristic curve selection similar to either GE IAC or ABB type curves

Field-selectable instantaneous or integrating reset

Field-selectable 50- or 60-hertz operation

Field-selectable 0.0 or 0.1 second, fixed, instantaneous delay

BE1-50/51B-219/-226

Introduction