Instantaneous Overcurrent (50) Element

Setting the INST PICKUP at the minimum pickup setting places the relay in the most sensitive state and
may be used as a safety setting.

BE1-50/51B-219 Pickup

Setting Range:

1 to 99 Aac

Setting Increment:

1 Aac

Accuracy:

±2%, ±25 milliamperes at or above 1.0 ampere setting

BE1-50/51B-226 Pickup

Setting Range:

0.2 to 19.8 Aac

Setting Increment:

0.2 Aac

Accuracy:

±2%, ±5 milliamperes at or above 0.2 ampere setting

Dropout

Dropout occurs at 95% of pickup value.

Curve Characteristics

Instantaneous characteristic curves are similar to standard electromechanical instantaneous units.
However, the time to trip for applications where the initial current through the relay is less than 0.4
ampere (5-ampere relay) or 0.08 ampere (1-ampere relay) may be slightly longer. This may occur on a
very lightly loaded circuit or when the relay is providing ground protection and is connected to measure
neutral current. Figure 10 shows the instantaneous characteristic curves for maximum time to trip.

1.0

10.0

100.0

0.000

0.200

0.400

0.600

0.800

1.000

1.200

Multiple of Pickup

x

R

D

(

S

e

c

o

n

d

s

)

P

0

0

4

6

-1

1

Vertical axis xRD (Seconds) is applicable for all curves and is derived from
multiplying the constant R for the curve selected times D (the Time Dial setting).

Specifications

BE1-50/51B-219/-226

Advertising
This manual is related to the following products: