Curve characteristics – Basler Electric BE1-50/51B-219 User Manual

Page 28

Advertising
background image

22

9252000981 Rev J

Maximum time dial
using 6.345 amperes:

61.3968 seconds

Curve time using 6.5 amperes: 53.1800 seconds

Curve Characteristics

Nine inverse time functions and one fixed time function can be selected by the front-panel Curve switch.
Characteristic curves for the inverse and definite time functions are defined by the following equation.

Where:

T

T

=

time to trip in seconds

D =

time dial setting

M

=

multiple of pickup setting

A, B, C, N, K =

constants for the particular curve

Time characteristic curve constants are listed in Table 3 and Table 4. Constants have been selected to
conform to the characteristics of electromechanical relays over a range of pickup multiples from 1.3 to 40.
Values of the constants are provided for use in computer relay setting software. Timing accuracy is

±1

cycle,

±2 percent of time to trip.

Table 3. Time Characteristic Curve Constants with SW3-3 Open (Off)

Curve Type

Figure

Number

Constants

BE1

Similar To

A

B

C

N

K

R

S

ABB CO-2

13

0.2663

0.03393

1.000

1.2969

0.028

0.500

L

ABB CO-5

14

5.6143

2.18592

1.000

1.000

0.028

15.750

D

ABB CO-6

15

0.4797

0.21359

1.000

1.5625

0.028

0.875

M

ABB CO-7

16

0.3022

0.12840

1.000

0.5000

0.028

1.750

I

ABB CO-8

17

8.9341

0.17966

1.000

2.0938

0.028

9.000

V

ABB CO-9

18

5.4678

0.10814

1.000

2.0469

0.028

5.500

E

ABB CO-11

19

7.7624

0.02758

1.000

2.0938

0.028

7.750

B

BS142-B ‡

20

1.4638

0.00000

1.000

1.0469

0.028

3.250

C

BS142-C ‡

21

8.2506

0.00000

1.000

2.0469

0.028

8.000

F

None §

N/A

0.0000

1.00000

0.000

0.0000

0.000

1.000

K

BD

C

M

AD

T

N

T

+

+

=

-

Specifications

BE1-50/51B-219/-226

Advertising
This manual is related to the following products: