Basler Electric BE1-50/51B-219 User Manual

Page 24

Advertising
background image

18

9252000981 Rev J

Step 3. Set INST PICKUP to 08.

Step 4. Slowly increase current to terminals 8 and 9. INST contacts should close at an input current of

1.563 to 1.637 amperes.

Step 5. Decrease input current until INST output contacts open.

Time Dial Test

Perform preliminary setup:

Connect test setup as shown in Figure 7.

Insure that SW3 switches are set: SW3-1 for the operating frequency, SW3-2 to OFF, SW3-3 to
ON, and SW3-4 ON.

Set TIME DIAL to 4.5.

Set CURVE to S

Set TIME PICKUP to 0.2.

Set INST PICKUP to 18.0.

Step 1. Prepare to apply 0.3 amperes input current to terminals 8 and 9 and record the elapsed time from

when current is applied until TIME output contacts close.

Step 2. Apply the current (step from 0 to 0.3 amperes) and record the elapsed time. Elapsed time should

be 0.345 to 0.424 seconds. (This tolerance is greater than ±2 % because it is the accumulation
of both pickup and timing tolerances.)

Step 3. Remove input current.

Target Test

Perform preliminary setup:

Connect test setup as shown in Figure 8.

Insure that SW3 switches are set: SW3-1 for the operating frequency, SW3-2 to OFF, SW3-3 to
ON, and SW3-4 ON.

Set TIME DIAL to 4.5.

Set CURVE to S

Set TIME PICKUP to 0.2.

Set INST PICKUP to 19.8.

Step 1. Set voltage source to provide a target current of 1.0 ampere.

Step 2. Apply 1 ampere input current to terminals 8 and 9. Check that the TIME target operates.

Step 3. Remove input current and reset target.

Step 4. Set TIME PICKUP to 3.18 and set INST PICKUP to 0.2.

Step 5. Set voltage source to provide a target current of 1.0 ampere.

Step 6. Apply 1 ampere input current to terminals 8 and 9. Check that the INST target operates.

Step 7. Remove input current and reset target.

Manual Trip Test

Perform preliminary setup:

Connect test setup as shown in Figure 8.

Insure that SW3 switches are set: SW3-1 for the operating frequency, SW3-2 to OFF, SW3-3 to
ON, and SW3-4 ON.

Set TIME DIAL to 4.5.

Set CURVE to S

Set TIME PICKUP to 0.2.

Set INST PICKUP to 0.2.

Testing

BE1-50/51B-219/-226