Specifications, Time overcurrent (51) element, Be1-50/51b-237 pickup – Basler Electric BE1-50/51B-237 User Manual

Page 12: Be1-50/51b-238 pickup, Dropout, Characteristic curves, Fixed timing, Reset, Instantaneous overcurrent a (50-a) element, Specifications -2

Advertising
background image

1-2

BE1-50/51B-237/-238 General Information

9252000899 Rev B

Internal switches provide for selecting system-operating frequencies of 50 or 60 Hz, instantaneous

element delays of 0.0 or 0.1 second, characteristic curve group selection for either GE IAC or ABB type

curves, and instantaneous or integrating reset characteristics. Switch location and description is provided

in Section 2.

Specifications

BE1-50/51B-237 and BE1-50/51B-238 electrical and physical specifications are listed in the following

paragraphs.

Time Overcurrent (51) Element

Setting Range ............................ 0.5 to 15.9 Aac

BE1-50/51B-237 Pickup

Setting Increment ....................... 0.1 Aac

Accuracy .................................... Sum of ±2% and ±25 mAac

Setting Range ............................ 0.1 to 3.18 Aac

BE1-50/51B-238 Pickup

Setting Increment ....................... 0.02 Aac

Accuracy .................................... Sum of ±2% and ±5 mAac

Dropout occurs at 95% of pickup value.

Dropout

Available curve types follow IEEE Standard C37.112 (1996) and emulate standard GE IAC, ABB CO, and

BS142 curves. Appendix A, Characteristic Curves illustrates the available curves and lists the applicable

constants.

Characteristic Curves

Curve Types .............................. Short Inverse, Long Inverse, Definite Time, Moderately Inverse, Inverse,

Very Inverse, Extremely Inverse, BS142 Very Inverse, BS142 Extremely

Inverse, Fixed Time

Time Multiplier ........................... 11 curves for each characteristic

Timing Accuracy ........................ ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap

and is for a given measured multiple of tap.

Setting Range ............................ 0.1 to 9.9 s

Fixed Timing

Setting Increment ....................... 0.1 s

Timing Accuracy ........................ ±1 cycle, ±2% of the time to trip for time dial settings ≥0.1.

Integrating .................................. Simulates the disk reset of electromechanical relays and begins when

the current decreases below 95% of pickup. Appendix A, Characteristic

Curves illustrates the integrating reset characteristic curve and equation.

Reset

Instantaneous ............................ Reset occurs within 16 ms of when the current decreases below 95% of

the pickup level.

Instantaneous Overcurrent A (50-A) Element

Setting Range ............................ 2 to 99 Aac

BE1-50/51B-237 Pickup

Setting increment ....................... 1 Aac

Accuracy .................................... Sum of ±2% and ±25 mAac

Setting Range ............................ 0.4 to 19.8 Aac

BE1-50/51B-238 Pickup

Setting increment ....................... 0.2 Aac

Accuracy .................................... Sum of ±2% and ±5 mAac