5-10

BE1-50/51B-237/-238 Testing

9252000899 Rev B

6. Connect a jumper to the Instantaneous Overcurrent Manual Trip jacks. Verify that the stop input of

the test set timer recognizes a 50-A contact closure

7. Remove the jumper and the current applied to relay terminals 5 and 6.