Be1-50/51b-238 burden, Frequency response, Transient response – Basler Electric BE1-50/51B-237 User Manual

Page 15: Harmonic rejection, Frequency response -5, Transient response -5, Harmonic rejection -5

Advertising
background image

9252000899 Rev B

BE1-50/51B-237/-238 General Information

1-5

Figure 1-4

BE1-50/51B-238 Burden

illustrates the current sensing input burden characteristic.

At 0.1 Aac .................................. 57.0 Ω

At 1.0 Aac .................................. 6.9 Ω

Figure 1-4. Current Sensing Input Burden (BE1-50/51B-238)

Frequency Response

A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for

pickup.

Transient Response

<10% overreach with system time constants up to 40 ms.

Harmonic Rejection

Rejection of odd and even harmonics is illustrated in Figure 1-5.

BE1-50/51B-234 CT Burden

0

20

40

60

80

100

120

140

0

2

4

6

8

10

Input Current (Amps)

Bu

rd

en

in

V

A (

rm

s)

BE1-50/51B-238 CT Burden