9252000899 Rev B

BE1-50/51B-237/-238 General Information

1-3

Dropout occurs at 95% of pickup value.

Dropout

Switch selectable—no intentional delay (SW3-2 open/off) or a fixed delay of 100 ms (SW3-2 closed/on).

Appendix A, Characteristic Curves illustrates the characteristic curve for the 50-A and 50-B elements.

Time Delay

Instantaneous Overcurrent B (50-B) Element

Setting Range ............................ 1 to 15.9 Aac

BE1-50/51B-237 Pickup

Setting increment ....................... 0.1 Aac

Accuracy .................................... Sum of ±2% and ±25 mAac

Setting Range ............................ 0.2 to 3.18 Aac

BE1-50/51B-238 Pickup

Setting increment ....................... 0.02 Aac

Accuracy .................................... Sum of ±2% and ±5 mAac

Dropout occurs at 95% of pickup value.

Dropout

Fixed at no intentional delay. Appendix A, Characteristic Curves illustrates the characteristic curve for the

50-A and 50-B elements.

Time Delay

Resets within 16 ms of when sensed current decreases below the pickup level.

Reset Characteristic

Current Sensing Input

Continuous Rating ..................... 14 Aac∗

BE1-50/51B-237

1 Second Rating ........................ 400 Aac

Continuous rating is 14 Aac for temperatures up to 45°C. See Figure 1-1 for derating curve.

Figure 1-1. Current Sensing Input Derating Curve (BE1-50/51B-237)


Continuous Current

Current Sensing Input

0

2

4

6

8

10

12

14

16

-40

-20

0

20

40

60

Ambient Temperature (C)

Cu

rre

nt

(Aa

c)

Advertising