BE1-50/51B-237/-238 General Information

9252000899 Rev B

Figure 1-5. Harmonic Rejection

Target Indicators

A gravity-latched, manually-reset, current-operated target indicator is provided for the time-overcurrent

(51) trip output and the instantaneous overcurrent A (50-A) trip output. A target indicator is not provided

for the 50-B trip output. The level of trip circuit current required to operate each target is individually

controlled by a circuit board jumper. See Section 2, Controls and Indicators for jumper locations and

function assignments

Jumper Position—Pins 1 and 2: 0.9 to 2.25 A ∗

Minimum Operating Current

Jumper Position—Pins 2 and 3: 80 mA to 200 mA ∗
*

Minimum operating current values. See Output Contacts for the maximum acceptable levels of trip

circuit currents.

Output Contacts

Output contacts are surge protected and rated as follows.

120/240 Vac ............................... Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3

amperes continuously, and break 5 amperes.

Resistive Ratings

125/250 Vdc ............................... Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3

amperes continuously, and break 0.3 ampere.

120/240 Vac, 125/250 Vdc ........ Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2

minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).

Inductive Ratings

51 Element ................................. 1, 2

Terminal Assignments

50-A Element ............................. 1, 2

50-B Element ............................. 1, 3