General

When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to

prevent damage during transit. Immediately upon receipt of a relay, check the model and part number

against the requisition and packing list to see that they agree. Visually inspect the relay for damage that

may have occurred during shipment. If there is evidence of damage, immediately file a claim with the

carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric,

Highland, Illinois.
Proper operation of the relay may be confirmed by performing the operational test procedure of Section 5.

If the relay will not be installed immediately, store the relay in its original shipping carton in a moisture and

dust-free environment.

Factory Settings

Factory settings for the internal switches of SW3 and jumper settings are as follows:

SW3-1 — OFF (60 hertz operation).

SW3-2 — OFF (0.0 additional fixed delay for the instantaneous element).

SW3-3 — ON (GE IAC type characteristic curves).

SW3-4 — ON (Integrating reset characteristics).

J1 pins 2-3 — 50-A minimum target operating current of 80 to 200 mA

J2 pins 2-3 — 51 minimum target operating current of 80 to 200 mA

Installation

Select the desired relay settings before putting the relay into service. Changing pickup current settings

while the relay is in service may cause tripping. Perform the following procedures to install the BE1-

50/51B-237 or BE1-50/51B-238 relay.

Select the desired relay settings on your new BE1-50/51B-237 or BE1-50/51B-238 relay.

Remove the existing IAC relay.

Use the four screws provided and attach the cover adapter to the existing case.

Insert the new relay and close the cradle latches locking the relay into the case.

Install the new Basler Electric connection plug.

To install the cover, position the interlocking bracket at the top of the new Basler Electric cover into

the mating receptacle at the top of the cover adapter plate. Secure the captive fastener at the bottom

of the cover.