Basler Electric BE1-51/27C User Manual

Page 52

Advertising
background image

46

9137200998 Rev E

Step 8. Set the front panel TAP selector to J.

Step 9. Slowly adjust the test set, increasing the overcurrent threshold toward the value of the front

panel TAP selector J setting until the front panel TIMING indicator just illuminates. Do not
disturb this setting.

Step 10. Record the current reading and remove input current.

RESULT: The recorded value should be within

±5% of the front panel TAP selector J setting for

the phase maximum overcurrent pickup point for the time overcurrent element.

Step 11. Perform the following steps as appropriate for the correct sensing input types.

Note

Ensure that the voltage sense terminals and current sense terminals
are connected to the same phase.

(a)

Sensing Input Type L (Single-Phase Sensing). This concludes the time overcurrent test.
Proceed to the timed output test.

(b)

Sensing Input Type J (Two-Phase and Neutral Sensing). Remove the power and
reconnect the input sensing to the remaining phases as shown in Figure 35, each time
repeating Steps 1 through 10. For neutral testing, continue with Step 12.

(c)

Sensing Input Type A and P (Three-Phase Sensing). Remove the power and reconnect
the input sensing to each of the remaining phases as shown in Figures 33 and 35, each
time repeating Steps 1 through 10.

(d)

Sensing Input Type D and U (Three-Phase with Neutral Sensing). Remove the power
and reconnect the input sensing to each of the remaining phases as shown in Figures 32
and 34, each time repeating Steps 1 through 10. For neutral testing, continue with Step
12.

Step 12. Perform the preliminary instructions.

For the neutral sensing (terminals 17 and 18), connect the relay as shown in Figures 32 and 34,

then perform the following steps (Steps 13 through 21).

Step 13. Set the front panel TAP (NEUTRAL) selector to A.

Step 14. Adjust the test set for an overcurrent threshold having one of the following values:

(a)

0.5 A for relays with Sensing Input Range 2 or 3.

(b)

1.5 A for relays with Sensing Input Range 4 or 5.

Step 15. Slowly adjust the front panel CAL (NEUTRAL) control CCW until the front panel TIMING

indicator illuminates.

RESULT: For the neutral minimum overcurrent pickup point of 0.5 A (Step 16a, above) or 1.5 A

(Step 16b, above) the front panel CAL (NEUTRAL) control should be near its maximum CCW
limit.

Step 16. Adjust the front panel CAL (NEUTRAL) control fully CW to allow measurement of the actual

overcurrent pickup point at the A setting of the front panel TAP (NEUTRAL) selector. Note that
the front panel TIMING (NEUTRAL) indicator will extinguish. Do not disturb this setting.

Step 17. Slowly increase the current toward the value of the front panel TAP (NEUTRAL) selector A

setting until the front panel TIMING (NEUTRAL) indicator illuminates. Do not disturb this
setting.

Step 18. Record the current reading and remove input current.

Tests and Adjustments

BE1-51/27C

Advertising