Introduction, Standard features, Time overcurrent functions – Basler Electric BE1-51/27C User Manual

Page 7

Advertising
background image

9137200998 Rev E

1

Introduction

BE1-51/27C Time Overcurrent Relays are microprocessor-based devices that monitor the magnitude of
line current to provide accurate time-overcurrent protection with undervoltage control (when the voltage
drops below the set point, the timing circuit is enabled). Instantaneous overcurrent element(s) and the
neutral time overcurrent element, when supplied, operate independently of the undervoltage function.
Each relay is available with one, three, or four time overcurrent elements.

BE1-51/27C relays provide backup protection for generators or transformers. Voltage control provides
discrimination between load and fault conditions by allowing the time overcurrent pickup to be set below
the maximum load (or swing) current. For sustained fault conditions, the synchronous reactance, X

d(unsat)

, is

typically larger than for normal load, X

d(sat)

. As a result, if the regulator is not in service, the three-phase

fault current will be less than the normal maximum load current. The relay pickup should be set below
rated maximum load current (e.g., 50 percent of rated) to ensure dependable backup. The BE1-51/27C
relay may also be used to provide primary phase fault protection for small generators or backup
protection for transformers.

When the BE1-51/27C is used to protect for faults on either side of a delta-wye power transformer, phase
overcurrent units should be supplied on all three phases (either three single-phase relays or one three-
phase relay). For this application, each phase time overcurrent element should be controlled by the
phase-to-ground voltage on its phase rather than by the phase-phase voltage.

Because the time overcurrent pickup of the phase element(s) does not vary with voltage level (the
element is either enabled or not depending upon voltage level), conventional time coordination
techniques apply.

A neutral (ground) overcurrent element can be applied and connected residually to a set of three current
transformers on solidly grounded applications or on impedance grounded systems that provide ground
fault current approximating the generator rated current level. The neutral element can also be connected
to a 10:1 ampere, zero-sequence window current transformer to provide protection on systems producing
a minimum of about 20 amperes primary current. Still another alternative would be connecting this device
to a current transformer in the neutral of a generator or power transformer.

Instantaneous elements can be used for transformer back-up applications when connected on the source
side of the power transformer. Because the pickup of these elements can be set above the relay current
flowing in the low-side fault, coordination can be achieved. Instantaneous overcurrent elements would not
ordinarily be used for a generator back-up function because they would not operate correctly for faults
external to the generator zone.

Under normal operating conditions, the phase time overcurrent pickup will be less than the maximum load
or non-fault current. As long as the rated voltage is applied to the relay, no operation will occur. However,
if a fuse opens on the voltage transformer and interrupts the signal, the relay will see this as a fault
condition (i.e., current level above pickup and voltage level below minimum set point) and operate
accordingly. The Basler Electric BE1-60 Voltage Balance Relay can prevent such a misoperation where
two sources of signal voltage are available. This relay compares the output of two signal sources, to
detect an anomaly in one of these sources and block the operation of those devices connected to that
signal source. Therefore, for generator applications, the Basler BE1-60 Voltage Balance relay should be
used in conjunction with the BE1-51/27C to prevent misoperations due to loss of the voltage source.

Standard Features

Time Overcurrent Functions

Time overcurrent elements pick up over a range of 0.1 to 0.8 amperes, 0.3 to 2.4 amperes, 0.5 to 4.0
amperes, 1.5 to 12.0 amperes, 0.1 to 2.4 amperes, or 0.5 to 12.0 amperes and provide an adjustable time
delay that is proportional to the overcurrent. Time delay is initiated when the sensed current exceeds the
pickup point. When the current drops below the pickup point, the timing circuit is reset immediately. At
reset, the output contacts, if operated, are restored to normal.

BE1-51/27C

Introduction

Advertising