Coordination with feeder 51 relay for fault 1 – Basler Electric BE1-51/27C User Manual

Page 63

Advertising
background image

9137200998 Rev E

57

Figure 36. System Example

Downstream current in Table 4 is the current in the downstream relay with which the BE1-51/27C
elements must coordinate. The currents are the changes resulting from the fault assuming a driving point
voltage of 11 kV. Actual currents will be the sum of the table values plus the pre-fault load currents.
Transient level currents are based on use of the generator transient reactance. Steady-state level
currents are based on use of generator steady-state reactance and assuming no generator regulator
boost. Note that the table values apply for 3-phase faults. Transient level currents in generators for a
phase-to-phase fault will be about equal to the 3-phase current values. Steady-state level currents in the
generators will be higher for a phase-to-phase fault.

Table 4. Three-Phase Fault Currents

Level

Out of Service

Fault Loc.

Fault Current - A @ 11 kV

Downstream

Generator

Transient

T2

1

7256

776

Steady State

T2

1

5961

129

Transient

2

7256

776

Transient

T2

2

1552

776

Steady State

T2

2

258

129

Transient

3

713

713

Steady State

3

127

127

Coordination with Feeder 51 Relay for Fault 1

(1)

Multiples of pickup in 51 relay at transient level:

(

)

7.6

960

7256

6

800/5

7256

=

=

BE1-51/27C

Tests and Adjustments

Advertising