Radio frequency interference (rfi), Isolation, Surge withstand capability – Basler Electric BE1-51/27C User Manual

Page 69: Ul recognized, Gost-r, Operating temperature, Storage temperature, Shock

Advertising
background image

9137200998 Rev E

63

Table 5. Power Supply Specifications

Type

Input Voltage

Burden at Nominal

Nominal

Range

O (mid-range)

48 Vdc

24 to 150 Vdc

1.6 W

P (mid-range)

125 Vdc
120 Vac

24 to 150 Vdc
90 to 132 Vac

1.9 W

8.9 VA

R (low-range)

24 Vdc

12 to 32 Vdc

*

1.7 W

S (mid-range)

48 Vdc

125 Vdc

24 to 150 Vdc
24 to 150 Vdc

1.6 W
1.9 W

T (high-range)

250 Vdc
240 Vac

68 to 280 Vdc
90 to 270 Vac

2.1 W

14.2 VA

* Type R power supply may require 14 Vdc to begin operation. Once operating, the voltage may be
reduced to 12 Vdc.

Radio Frequency Interference (RFI)

Field-tested using a five-watt, hand-held transceiver operating at random frequencies centered around
144 MHz and 440 MHz, with the antenna located six inches from the relay in both horizontal and vertical
planes.

Isolation

In accordance with IEC 255-5 and ANSI/IEEE C37.90, one-minute dielectric (high potential) tests as
follows:
All circuits to ground ........................ 2,121 Vdc
Input to output circuits ..................... 1,500 Vac or 2,121 Vdc

Surge Withstand Capability

Qualified to ANSI/IEEE C37.90.1-1989, Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems.

UL Recognized

UL recognized per Standard 508, UL File No. E97033. Note: Output contacts are not UL recognized for
voltages greater than 250 volts and input power supply voltages greater than 150 volts.

GOST-R

GOST-R certified per the relevant standards of Gosstandart of Russia.

Operating Temperature

The operating temperature range is from

−40°C (−40°F) to +70°C (+158°F).

Storage Temperature

The storage temperature range is from

−65°C (−85°F) to +100°C (+212°F).

Shock

In standard tests, the relay has withstood 15 g in each of three mutually perpendicular planes without
structural damage or degradation of performance.