Product overview

28

Embedded PC

CX9000-N031 connections

The CX9000-N031 system interface features two RS422 / RS 485 interfaces, COM1 and COM2 (9 pin Sub-D plug
connector). The maximum baud rate on all channels is 115 kBit. The pin assignment for all interfaces is equal and
described below. The interface parameter can be set in the operating system or in the PLC program.

RS232 COM interface (connector):

Pin assignment COM interface:

PIN

Signal

Type

Description

2

TxD+

Data-Out +

Transmit 422

3

RxD+

Data-In +

Receive 422

5 GND

Ground

Ground

6 VCC

VCC

+5V

7

TxD-

Data-Out -

Transmit 422

8

RxD-

Data-In -

Receive 422


For RS 485 Pin 2 and 3 ( Data +) as well as Pin7 and 8 (Data -) have to be connected..