Setting the interface parameter, Settings dip switches rs485 – BECKHOFF CX9000 User Manual

Page 31

Advertising
background image

Product overview

Embedded PC

29

Setting the interface parameter

If the system interface CX9000-N031 resides at the end of the CX9000-system block, it is easy to access the dip
switches. The dip switches for the configuration of the RS485/422 interfaces can be found at the left side of the
module. If you remove the grey cover you can see the switch:

The upper switch sets the parameters for the upper interface, the lower switch sets the parameter for the lower
interface. The system must be powered down, if the settings of the switches are changed! The settings for default
use should be mentioned by ordering the interface module.

Settings DIP switches RS485:

RS485 without Echo, End-Point ( Terminated) DEFAULT setting

DIP

Status

Function

1 off

Echo

on

2 on

Echo

off

3 on

Auto

send

on

4

off

Always send on

5

on

Auto receive on

6

off

Always receive on

7 on

Term

on

8 on

Term

on

RS485 with Echo, End-Point ( Terminated)

DIP

Status

Function

1 on

Echo

on

2 off

Echo

off

3 on

Auto

send

on

4

off

Always send on

5

off

Auto receive on

6

on

Always receive on

7 on

Term

on

8 on

Term

on