Performance Data

Supply Air Temperature Rise

20°F

30°F

40°F

50°F

60°F

70°F

80°F

90°F

100°F

Model

Input

(BTU/hr)

CFM

50

50,000

1852

1235

926

741

617

529

463

412

370

75

75,000

2778

1852

1389

1111

926

794

694

617

556

100

100,000

3704

2469

1852

1481

1235

1058

926

823

741

125

125,000

4630

3086

2315

1852

1543

1323

1157

1029

926

150

150,000

5556

3704

2778

2222

1852

1587

1389

1235

1111

175

175,000

6481

4321

3241

2593

2160

1852

1620

1440

1296

200

200,000

7407

4938

3704

2963

2469

2116

1852

1646

1481

225

225,000

8333

5556

4167

3333

2778

2381

2083

1852

1667

250

250,000

9259

6173

4630

3704

3086

2646

2315

2058

1852

275

275,000

10185

6790

5093

4074

3395

2910

2546

2263

2037

300

300,000

11111

7407

5556

4444

3704

3175

2778

2469

2222

325

325,000

12037

8025

6019

4815

4012

3439

3009

2675

2407

350

350,000

12963

8642

6481

5185

4321

3704

3241

2881

2593

400

400,000

14815

9877

7407

5926

4938

4233

3704

3292

2963

Start-Up / Standby

Prior to start-up, verify that all field-installed sensors
have been installed. This includes a room temperature
sensor (optional) and a discharge air temperature sensor
(typical).

Heat Mode

When the unit or furnace controller calls for heat:

1. The ignition control will check that the pressure

switch for the combustion blower is open.

2. The combustion blower will energize and the

15 second pre-purge begins.

3. The gas valve is energized and the igniter will spark

for up to 10 seconds. If a flame is not sensed during
the trial for ignition, two additional tries will be
attempted before going into lockout for one hour.

4. When a flame is sensed, sparking stops immediately.

The gas valve and combustion blower remain
energized.

5. Ignition

4:1 Electronic Modulation - The burner will light at
100% fire and remain there for up to 30 seconds.
The main burner gas valve will then modulate from
100% down to a minimum of 25%, as needed.
The combustion blower will change between high
and low speed to maintain acceptable combustion
airflow. If the high speed pressure switch does not
pull in when required, the furnace will lock out.

8:1 Stage Control - The furnace controller will ignite
the necessary manifolds at 100% for 30 seconds,
after which the unit or furnace controller will operate
the manifolds at high and low fire. Each time a
manifold is initialized, the manifold will ignite at
100%.

Single Stage Control - The burner will light at
100% and remain at high fire.

Two Stage Control - The burner will light at 100%
fire and remain there for 10 seconds. The unit or
furnace controller will operate the burners at either
high or low fire, depending on the demand for heat.

6. The ignition control constantly monitors the call for

heat, the pressure switch and the burner flame to
assure proper operation.

7. When the unit or furnace controls are satisfied,

the main gas valve is then de-energized and the
combustion blower shuts off following a 30 second
post-purge period.

Recovery from Lockout

If the furnace goes into lockout, the ignition control will
automatically reset after one hour if the thermostat is
still calling for heat. If needed, a manual reset can be
accomplished by either shutting off the power or turning
off the call for heat (turn off the thermostat) for a period
of five seconds.

Sequence of Operation