Troubleshooting – Greenheck PVF/PVG Indirect Gas-Fired Heat Modules (474645) User Manual

Page 26

Advertising
background image

Indirect Gas-Fired Heat Modules

26

®

Ignition controller (IC#)

red LED blinks

7 times or is on

Ignition controller(s) (IC#) failed

Replace faulty ignition controller(s)

Yes

... continued from

previous page.

Does the combustion relay

(R9 or CR) close?

Internal high limit tripped (temperature above set point)

Let temperatures cool

Internal inlet air sensor open

Adjust inlet air sensor setting

(refer to Reference - FX Controller, Access the Inlet Air Sensor section)

Combustion relay (R9 or CR) defective

Replace defective combustion relay (R9 or CR)

No

Yes

Does the combustion

blower (CM) run?

Combustion blower fuse (FU9) blown

Replace combustion blower fuse (FU9)

Combustion blower (CM) defective

Replace defective combustion blower (CM)

No

Yes

No

Ignition controller (IC#)

red LED blinks

1 time, 2 times or 4 times

No

Cycle power to the unit

and wait 30 seconds

Everything is working properly,

consult factory.

Improper manifold pressure

Set high and low manifold pressure

(refer to 8 Staged Start-Up section)

Faulty spark rod or spark gap does not equal 1/8 inch

Replace spark rod or adjust gap to 1/8 inch

Yes

Does the combustion

blower stop after

30 seconds of operation?

Airflow switch (PS2) defective

Replace defective airflow switch (PS2)

Airflow relay (R9) defective

Replace defective airflow relay (R9)

Yes

No

With the combustion blower

(CM) on for at least

30 seconds, is there

24 VAC across T and A or E?

Furnace controller (SC1) defective

Replace furnace controller (SC1)

No

Yes

8 Stage Furnace Will Not Light

In all cases, verify correct terminals as shown on the unit-specific wiring diagram.

Troubleshooting