Troubleshooting – Greenheck PVF/PVG Indirect Gas-Fired Heat Modules (474645) User Manual

Page 23

Advertising
background image

Indirect Gas-Fired Heat Modules

23

®

4:1 Modulating Furnace Will Not Light

In all cases, verify correct terminals as shown on the unit-specific wiring diagram.

Troubleshooting

Ignition controller (IC#)

red LED blinks

7 times or is on

Ignition controller(s) (IC#) failed

Replace faulty ignition controller(s)

High limit switch (HLC#) open?

Discharge temperature was above high limit setting

Let cool then reset high limit.

Yes

Yes

No

Ignition controller (IC#)

red LED

blinks 6 times

Pressure switch (PS2) failure

Repair or replace pressure switch (PS2)

Combustion blower (CM) not functioning

Replace fusing (FU7), combustion blower or relay (CM)

Yes

No

Ignition controller (IC#)

red LED blinks

1 time, 2 times or 4 times

Improper manifold pressure

Set high and low manifold pressure

(refer to 4:1 Electronic Modulation Start-Up section)

Faulty spark rod or spark gap does not equal 1/8 inch

Replace spark rod or adjust gap to 1/8 inch

Yes

No

...continued from previous page

Secondary transformer (TR6) defective

Replace secondary transformer (TR6)

Furnace controller (SC1) defective

Replace furnace controller (SC1)

No

24 VAC between 24 VAC terminals

on mod valve

No

Yes

No

Yes

10 VDC between terminals

(+) and (-) on mod valve

Everything is working properly,

consult factory.