Troubleshooting – Greenheck PVF/PVG Indirect Gas-Fired Heat Modules (474645) User Manual

Page 27

Advertising
background image

Indirect Gas-Fired Heat Modules

27

®

Single or 2:1 Stage Furnace Will Not Light

In all cases, verify correct terminals as shown on the unit-specific wiring diagram.

Troubleshooting

Ignition controller (IC#)

red LED blinks

7 times or is on

Ignition controller (IC1) failed

Replace ignition controller.

High limit (HLC1) open?

Discharge temperature was above high limit setting

Wait for high limit to cool and reset.

24 VAC across A and 21?

Discharge air selector (TS2) improperly set or faulty

Adjust inlet air sensor setting (refer to Reference - FX Controller/ Access

the Inlet Air Sensor section)

Furnace stage one contact (SC1) defective (stage only)

Replace furnace stage one contact

24 VAC across 22 and 21?

Heating Transformer (TR2) Fault

Replace heating transformer

Yes

No

No

Yes

No

Yes

Yes

24 VAC across W1 and C?

Heat Switch (S4) open

Turn heat switch (S4) on

No

Yes

24 VAC across R and C?

Main disconnect (DS1) open or defective

Close, repair or replace

Main transformer (TR1) fault

Replace main transformer

No

Yes

Ignition controller (IC#)

red LED

blinks 6 times

Combustion blower (CM) not functioning

Replace combustion blower or relay (CR)

Air proving switch (PS2) defective

Replace air proving switch

Yes

No

Ignition controller (IC#)

red LED blinks

1 time, 2 times or 4 times

Improper manifold pressure

Set high and low manifold pressure (refer to Single Stage or

2:1 Staged Control Start-Up section)

Faulty spark rod or spark gap does not equal 1/8 inch

Replace spark rod or adjust gap to 1/8 inch

Yes

No

Everything is working

properly, consult factory.

Yes

24 VAC across 24 VAC and

21 on SC1 controller?

Optional inlet air sensor (TS4) open

Adjust setting reference start up

Heat relay (RH) is not energized

Check for loose connections. Repair or replace heat relay (RH)

No

Yes