Troubleshooting – Greenheck PVF/PVG Indirect Gas-Fired Heat Modules (474645) User Manual

Page 25

Advertising
background image

Indirect Gas-Fired Heat Modules

25

®

8 Stage Furnace Will Not Light

In all cases, verify correct terminals as shown on the unit-specific wiring diagram.

Troubleshooting

With the combustion blower

(CM) off, is the N.O.

airflow switch (PS2) closed?

Continues on next page...

Airflow switch (PS2) defective

Replace defective airflow switch (PS2)

Yes

No

24 VAC across terminals

S and T?

Discharge temperature was above high limit control (HLC1)

Wait for high limit to cool and reset

Inlet air sensor contact open

Adjust inlet air sensor setting

(refer to Reference - FX Controller, Access the Inlet Air Sensor section)

Furnace controller (SC1) defective

Replace furnace controller (SC1)

24 VAC across 22 and 21?

Heat transformer (TR2) fault

Replace heating transformer

No

No

Yes

Yes

N.O. contact on heat relay (RH)

closed?

Heat relay (RH) is not energized

Check for loose connections. Repair of replace heat relay (RH)

No

Yes

24 VAC across W1 and C?

Heat switch (S4) open or not wired

Close or replace heat switch (S4)

No

Yes

24 VAC across R and C?

Main disconnect (DS1) open or defective

Close, repair or replace

Main transformer (TR1) fault

Replace main transformer

No

Yes

DT1 displayed on furnace

controller (SC1)?

Discharge air sensor (TS2) not wired or defective

Wire or replace discharge air sensor (TS2)

Yes

No

OT1 displayed on furnace

controller (SC1)?

Outdoor air sensor (TS1) not wired or defective

Wire or replace outdoor temperature sensor (TS1)

Yes

No

Blank screen on furnace

controller (SC1)?

Furnace controller (SC1) defective or not powered

Replace or wire furnace controller (SC1)

Yes

No