Troubleshooting – Greenheck PVF/PVG Indirect Gas-Fired Heat Modules (474645) User Manual

Page 24

Advertising
background image

Indirect Gas-Fired Heat Modules

24

®

2:1 Modulating Furnace Will Not Light

In all cases, verify correct terminals as shown on the unit-specific wiring diagram.

Troubleshooting

Ignition controller (IC#)

red LED blinks

7 times or is on

Ignition controller (IC1) failed

Replace ignition controller

24 VAC across A and X?

Discharge air selector (TS3) improperly set or faulty

Adjust setting (see staged start-up) or replace sensor

24 VAC across S and X?

Heat transformer (TR5) fault

Replace heating transformer

Discharge temperature was above high limit control (HLC1)

Wait for high limit to cool and reset.

No

No

Yes

Yes

Yes

24 VAC across W1 and C?

Heat switch (S4) open or not wired

Close or replace heat switch (S4)

No

Yes

24 VAC across R and C?

Main disconnect (DS1) open or defective

Close, repair or replace

Main transformer (TR1) fault

Replace main transformer

No

Yes

Ignition controller (IC#)

red LED

blinks 6 times

Combustion blower (CM) not functioning

Replace combustion blower or relay (CM)

Air proving switch (PS2) defective

Replace air proving switch

Yes

No

Ignition controller (IC#)

red LED blinks

1 time, 2 times or 4 times

Improper manifold pressure

Set high and low manifold pressure

(refer to the 2:1 Electronic Modulation Start-Up section)

Faulty spark rod or spark gap does not equal 1/8 inch

Replace spark rod or adjust gap to 1/8 inch

Yes

No

Everything is working

properly, consult factory.

Yes

24 VAC across 29 and X?

Optional inlet air sensor contact (TS4 open)

Adjust inlet air sensor setting

(refer to Reference - FX Controller, Access the Inlet Air Sensor section)

Heat relay (RH) is not energized

Check for loose connections. Repair or replace heat relay (RH)

No

Yes