Herrtronic, Model 6000 – Herrmidifier Herrtronic 6000 Series User Manual

Page 10

Advertising
background image

Herrtronic

®

Model 6000

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

10

www.herrmidifier-hvac.com

SECTION IV OPERATING INSTRUCTIONS

Start-up Instructions

1. Check that the humidifier is properly mounted and level.

2. Check that the water fill and drain are properly connected.

3. Check that the correct voltage and amperage service are

supplied.

4. Check all controls are wired properly.

5. Check that the steam distributor is properly installed and

that the steam hose has been properly routed without any

kinks or flat spots.

6. With power off, double check all electrical connections and

plumbing connections to insure that they did not loosen dur-

ing shipment.

7. With the “on-off-drain” switch in the “off” position, and the

control and high limit (ducted versions only) humidistats

at their lowest settings, turn on the main disconnect. The

contactor should remain deenergized and the power light

should remain “off”. Place the “on-off-drain” switch in the

“on” position and the power light should illuminate.

8. Turn the control and high limit (ducted versions only) hu-

midistats up to their highest setting. The contactor should

pull in.

9. After approximately a 5 second delay, the fill valve ener-

gizes and water begins to fill the cylinder to the preset amp

level or cylinder full condition, depending on the incoming

water supply. When starting up the unit, it is best to put an

amp clamp on the power leg that passes through the

NOTE:

If upon initial start-up of this humidifier the cylinder is

slow in heating and/or the service light continues to come

on, drain the tank to 1/4 full. Turn off power at breaker, ob-

tain some Alka-Seltzer tablets and crumble 1/2 of one tab-

let (Alka-Seltzer) into the grey fill tee. Change the middle

blue dial on the left side of the circuit board, R18, from

90% to 87%. Then turn the breaker on and run the unit. If

you have had to use these this step on a 240V unit (6000-

2,4), it is advisable that you order a GT-176-1 replacement

cylinder rather than the standard replacement cylinder in

the future so this procedure will not need to be repeated.

Upon receipt of the GT-176-1 cylinder, adjust the dial,

R18, on the circuit board back to 90%.

toroid transformer. Insure that the humidifier fills to “cylinder

full” (approximately 1.5” from the top of the cylinder), or that

the amperage reaches the data plate maximum and the fill

valve de-energizes.

10. All units are equipped with a drain tempering feature which

mixes cold fill water with the hot drain water to protect drain

piping. Depending on your fill water pressure, some adjust-

ment of the fill metering valve may be necessary to insure

drain water of less than 140°F (See Figure 9). To deacti-

vate, remove diode from socket CRI8 from circuit board

(See Figure 12).

11. Reset control and high limit humidistats to their desired set-

tings. Typical control humidistat settings are 30-40% and

the high limit humidistat settings are 65-70%.

NOTE:

The capacity of the humidifier can be adjusted between

50% and 100% of the maximum level by adjusting the

capacity adjustment potentiometer (labeled R39) on the

main circuit board. All blower versions are set from the

factory to produce 4 lbs/hr. If the psychrometric condi-

tions permit, the 6000—2 may be increased to 8 lbs/hr

by adjusting R39 from 50% to 100% capacity. Refer to

figure 12.

CAUTION!

Inadequate airflow may allow humidity to collect in areas

causing condensation.

Figure 9

VIEW IN FROM RIGHTSIDE OF UNIT

TRANSFORMER

L1 L2

RELAY

TERMINAL BLOCK

FILL VALVE

MOUNTING SCREWS

FILL VALVE

ADJUSTING SCREW

CYLINDER FULL

INTERFACE