Model 6000

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

14

www.herrmidifier-hvac.com

Unit Detected Faults: (Red Service Light is ON)

Problem / Symptom

Probable Cause

Reason - Correction

Overcurrent

The alarm condition occurs when an

overcurrent situation (>138% of rated

current) has occurred and the humidifier

has shut down to prevent any damage.

This alarm indicates that there has been

a significant reduction in resistance be-

tween the main legs of the supply power

and the humidifier has been shut down to

prevent damage and should be serviced

before it is restarted. Overcurrent LED

CR 17 (Figure 12) is illuminated.

Dead short between electrodes.

Replace the steam cylinder. Check re-

sistance between electrodes with power

“off”

Restricted or blocked drain.

Clean and inspect drain system.

Restricted fill system

Clean and inspect the fill system. Check

for restriction or loss of supply pressure.

Incoming water conductivity is outside

the range of normal circuit board settings.

Consult the factory for options.

Check amp draw to unit during start-up.

If amp draw greatly exceeds rated amp

draw, the drain threshold pot, labeled

“% adj.” (R18), must be increased 2% to

increase the frequency and duration of

drains to reduce the conductivity inside

the cylinder.

Manually drain the unit and restart.

End of Cylinder

This alarm condition occurs if the humidi-

fier is unable to reach full output over a 6

hour timeframe. It is constantly switching

between “fill” and “cylinder full” modes.

This alarm indicates a need to change

the cylinder, that the water supply is low

in conductivity, or that a foaming condi-

tion exists:

End of cylinder life – Cylinder life is

typically between 500 and 2000 hours,

depending on incoming water supply.

For emergency use, you may restart the

humidifier with the capacity setpoint,

R39, at a lower level to allow operation

until a replacement steam cylinder can

be obtained. To clear the fault, turn the

main disconnect to the unit “off” and then

back “on”.

If incoming water supply is less than 100

micromho, the unit may not be able to

pass the rated current through the water.

See – NON-FAULT ACTIVATED PROB-

LEMS GUIDE – “Unit fills to the cylinder

full condition and remains cold”

Foaming condition exists.

Flush and fill the steam cylinder several

times and restart. If it persists, you must

filter or treat the water to remove the

foaming agent. See circuit board settings

on previous page if supply water is soft-

ened. See NON – FAULT ACTIVATED

PROBLEMS GUIDE – “Water foaming

inside the cylinder”

Fill System Fault

This alarm condition occurs when the fill

valve has been energized for a 6 hour

timeframe. The humidifier has been

shutdown to prevent any damage.

Loss of or restricted water supply

Check fill system.

Leaking drain system.

Check drain system.

Defective drain valve.

Repair and replace as required.

Defective fill valve.

Repair and replace as required.

NOTE: The three fault conditions outlined above will cause the humidifier to shut down and the service light on the front

of the unit to illuminate. To clear these faults, the main power must be turned “off” and back “on” again.