Wiring

All field wiring should be routed up through the knockout in the

bottom panel or in the back of the unit.

Figure 7

Supply Power

1. Insure that minimum circuit ampacity is 15 amps.

2. Terminals are provided in the electrical compartment for

field connection of the main power supply legs (single

phase) and a ground wire.

3. Install external overcurrent protection and provide wiring in

accordance with the NEC, state and local codes.

4. Power supply must be “clean”: free of spikes, surges and

sags: -15% to +10% of nominal.

Electrical Characteristics:

Capacity

Steam Output

Lbs. / hr

4

8

Kg / hr

1.8

3.7

Input KW

1.33

2.66

Volts/Ph:

Amps

120/1

11.8

N/A

230/1

5.9

11.8

Control Circuit Connections

WARNING!

Do Not install any controls inside the Herrmidifier 6000

cabinet. Installations of any extraneous devices inside

the electrical compartment rnay cause erratic behavior of

the circuitry and will VOID the warranty.

6000-1,2

The 6000 units with built-in blowers require no external control

wiring since the humidistat is built-in.

6000-3,4

The control wiring for the ducted version is to be connected to

the 5 pole controls terminal strip located in the low voltage com-

partment. Terminals #1 and #2 are for connecting the control

and high limit humidistats as well as the air proving switch in se-

ries (all included). If desired, terminals #3 and #4 are relay con-

tacts to energize your fan relay (Relay contact rating 12 Amps

at 125 VAC, 8 Amps at 250 VAC). With this optional wiring, on a

call for humidity, the humidifier will close the interlock relay and

energize the fan blower. The air proving switch must not be used

if the fan interlock is utilized. All control wiring should be 22 AWG

or larger (See figure 8). Consult with the factory if you have any

special wiring requirements.

Figure 8

BOTTOM VIEW

1 3/8"

3 3/4"

1"

1 1/2"

2" KNOCKOUT

7/8" KNOCKOUT

FAN

INTERLOCK

(OPTIONAL)

4

3

2

1

AIR-PROVING

SWITCH

HIGH LIMIT

HUMIDISTAT

NOTE: AIR PROVING SWITCH MUST NOT BE USED

WHEN INCORPORATING FAN INTERLOCK OPTION.

TERMINAL

STRIP

SWITCH