Herrtronic, Model 6000 – Herrmidifier Herrtronic 6000 Series User Manual

Page 5

Advertising
background image

Herrtronic

®

Model 6000

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

5

www.herrmidifier-hvac.com

Key Features

Adjustable Setpoints:

Capacity

• Range = 50-100%

• Preset at 100% for 6000-1,3,4

• Preset at 50% for 6000-2

Low Drain Threshold

• Range = 50-100%

• Preset at 90%

Cycle Time

• Range = 30-180 seconds

• Preset at 60 seconds

Faults:

Overcurrent

• 138% of Rated Current

• System Shutdown

Fill System

• Fill valve open for 6 hours without achieving capac-

ity setpoint or cylinder full

• System Shutdown

End of Cylinder Life

• 6 hours of operation while on cylinder full without

achieving capacity setpoint.

• System Shutdown

• Operation using water of less than 100 micromho

is not recommended.

• Typically 500-2000 hours of cylinder operation can

be obtained. Your actual cylinder life may be higher

or lower depending on the exact composition of

your water supply.

HERRMIDIFIER

POWER, CYLINDER FULL,

AND SERVICE INDICATOR LIGHTS

INTERNAL CIRCUIT BREAKER

ON/OFF/DRAIN SWITCH

COVER INTERLOCK SWITCH

(PREVENTS UNIT OPERATION

WITH COVER OFF)

FILL SYSTEM

(INTEGRAL 1" AIR GAP PREVENTS

REVERSE SIPHONING TO POTABLE

WATER SUPPLY; "ADJUSTABLE

METERING VALVE ACCOMODATES

WATER PRESSURES UP TO 100 PSI."

ISOLATED CONTROL COMPARTMENT

WITH SOLID STATE CONTROLS

DRAIN SYSTEM

(SEALED DRAIN VALVE, ADJUSTABLE

DRAIN THRESHOLD AND CYCLE

TIME PROVIDE EXTENDED LIFE.)

CYLINDER - REPLACEABLE

GLASS FILLED POLYPROPYLENE

"CYLINDER FULL" ELECTRODE

(RED WIRE)

ADJUSTABLE LOUVER

(6000-1, -2 UNIT)

INTEGRAL, QUIET

OPERATING FAN

(6000-1, -2 UNIT)

CONCEALED FILL AND

DRAIN CONNECTIONS

INTEGRAL HUMIDISTAT

(6000-1, -2 UNIT)