Installation – Montigo H38DF ST User Manual

Page 14

Advertising
background image

H*38DF ST Indoor Gas Fireplace

Page 14

XG0207 - 150204.1

Installation

The Venting Graph:

Measure the vertical height from the fireplace hearth to the centre of the

termination and the horizontal run from the fireplace flue collar to the wall

flange of the termination. Plot on the Venting Graph Figure 13 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 114" and the horizontal

run to the wall flange of the vent termination is 168", this would be

an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 36" and the horizontal

run to the wall flange of the vent termination is 84", this would

NOT be an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 60" and

the horizontal run to the wall flange of the vent termination is 144",

this would NOT be an acceptable installation.

Figure 13. Top Vent Venting Graph for wall mounted terminations.

Figure 13a. Top Vented, wall mounted installation with one 90° bend. The vent

run must comply with Venting Graph for Top vent, wall mounted terminations,

Figure 13.

Figure 13b. Top Vented, wall mounted Multi-elbow installation. See Venting

Graph for Top vent, wall mounted terminations, Figure 13.

Section 3-3-1: Venting Layout: Wall mounted termination.

Selection of components and details of venting layout should adhere

to the following guidelines:

„

Vent terminations must not be recessed in walls or siding.

„

For Heat Shield requirements see Section 3-3-3.

„

Once the proposed venting layout has been determined refer to

Figure 13 or 14 to ensure the layout is acceptable.

Notes Wall Mounted Terminations: TOP VENT

„

All measurements for vertical or horizontal runs are measured

from center of the vent pipe.

„

Venting runs must fall within the limits set by the venting graph,

see Figure 13.

42”

46”

A

C

B

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

If your installation does not fall within

the venting graph parameters,

please contact a local Montigo dealer

for Power Venting Options.

Heat Shield

42” Max.

46”Min.

Termination

Exterior

Wall

Hearth

Solid Section

Flex Section

Hearth

15’ foot Max.

Heat

Shield

Termination

Exterior

Wa

ll

Advertising
This manual is related to the following products: