Clearances, Installation – Montigo H38DF ST User Manual

Page 9

Advertising
background image

H*38DF ST Indoor Gas Fireplace

Page 9

XG0207 - 150204.1

Installation

Clearances

When installing a shelf over the top of the fireplaces, the following

guidelines must be adhered to:
For Side Vent applications, the minimum clearance is 2" from the side of

the fireplace to a wall, or any combustible materials, and 10" clearance

from the top of the fireplace to the underside of any combustible shelf

materials.
For Top Vent applications, the minimum clearance is 2" from the side

of the fireplace to a wall, or any combustible materials, and 17 1/2" to

the underside of any combustible shelf materials.
1” clearance is maintained on sides and bottom of vent runs and 2”

above horizontal vent runs to any combustible material.

H*38DF*-ST 10"

17 1/2"

2"

0"

**

MODEL

Top - Side V

ent

Top - T

op V

ent

Sides

Floor

Mantel

6”

Installing The Standoffs

To avoid elevated mantel temperatures, all H*38DF*-ST gas

fireplaces are required to have the supplied standoffs installed.

The fireplace is supplied with four standoffs. Bend and install these

standoffs on top of the fireplace ensuring that the height of the standoff

maintains a 6" clearance.

Figure 7. Installing the standoff's (Both sides typical).

Figure 8. Installing the Nailing Flange Extension (Both sides typical).

6"

Installing the Nailing Flange Extension

Once the fireplace is placed into the rough framed opening, the supplied

Nailing Flange Extension (Part No. H42074) must be fasten securely

into place, with nails or wood screws. as shown in Figure 8.

The Supplied nailing extension must be placed along the top edge of the

fireplace and securely fastened in place to the non combustible header

and combustible wood framing.

Note: The nailing flange extension can be substituted with a piece of

NON-Combustible material of the same size and thermal characteristics,

ie: cement board or equivalent. This is recommended in applications

where the facing materials will not adhere to the metal nailing flange.

Note: Clearance from top of fireplace to a ceiling within the fireplace

enclosure.

** Note: For mantel clearance, please refer to Section 6: Finishing

on page 21.