Section 3: finishing, Installation – Montigo R320-ST User Manual

Page 10

Advertising
background image

Step2. Back-framing the Fireplace; installing 2 x 4's, (Typical Both

sides). Ensure you have the required 2 x 4's to complete the project.

Cut Four (4) - 2 x 4's to fit under the front & rear fireplace throat,

(horizontal), fit & remove. These must be no closer than 3" below

the bottom edge of glass. Next, cut the short 2 x 4's, to fit at each

end under the previous Horizontals.

Next, cut the required quantity of short filler 2x4's under the lower

Horizontal. The number of pieces will be determined by the length,

and model of fireplace. (Follow Typical building codes and practices

when spacing). Next, cut the Required Left and Right Vertical 2 x 4's

and space at 3" from side of apron. Install the Two Non-combustible

Headers (one per side), supplied by Montigo, as per Figure 3.

Step1:Removescrewsfromperimeterofglassasshown

below. The screws will be used to fasten the cement board,

provided by Montigo, to the unit in the finishing stages. Remove

the marked screws above and below the glass. Place provided

template to check screw hole positioning. Transfer template to

provided cement board to pre drill pilot holes. Refer to figures

below for Screw locations.

R420

4 Screws Top

&

4 Screws

Bottom

Front View

Side View

Figure 1 Sec.3 R320 Fireplace Screw Locations. Both Sides are Typical.

R320

3 Screws Top

&

3 Screws

Bottom

Front View

Side View

Figure 2 Sec.3 R420 Fireplace Screw Locations. Both Sides are Typical.

Section3:Finishing

Figure 3 Sec.3 Fireplace installation, (Ensure you maintain the 3" clearance to combustibles) Both Sides are Typical.

1"

Clearance

1"

Clearance

3” Clearance

to combustibles

3" Clearance

to combustibles

Non-combustible Header

(Supplied by Montigo)

2 X 4, (Top

Horizontal)

2 X 4, (Bottom

Horizontal)

2-pcs 2 x 4, (vertical)

Both Sides Typical

Both

Sides

Typical

First wood header installed

at 19” from top of glass

3” Clearance to

combustibles

First

combustible

(2) 2X4s

Space supplied

Non-Combustible Header(s)

to allow 6” of Cement board

to be fastened to

2 X 4 fillers, (Vertical) use typical

building practices when spacing

Space between

2 x 4s

R320 = 47½”

R420 = 59½”

Note: Images are shown without screens for clarity

purposes. However, your fireplace should not be

operated without proper installation of screens.

R320-ST & R420-ST Power Vent Indoor Gas Fireplace

Page 10

XG0774 - 150121

Installation