Installation – Montigo R320-ST User Manual

Page 15

Advertising
background image

Venting Layout

Selection of components and details of venting lay out should adhere

to the following guidelines:

■ Ensure there is a minimum run of 2’ of straight pipe before

the power vent.

■ Ensure the maximum vent run does not exceed 100’.

■ Ensure the number of 90° elbows does not exceed 6.

■ Ensure the number of 45° elbows does not exceed 12.

Figure 4 Sec.4 Typical Venting Installations.

Multi-Elbow Installations

Multi-elbow installations are possible up to a maximum of six

at 90° elbows.

Figure 5 Sec.4 PVHIN58-300 Power Vent.

Figure 6 Sec.4 Multi-elbow Venting Installations.

Downward Vertical Venting

Note: The downward vent run must not exceed 6' of vent run.

Installing a Wall Mounted Horizontal Exterior Power Vent

This section applies to installations where the shortest possible vent

run is through an exterior wall. Refer to Appendix A - Power Vent

locations, to ensure the planned Power vent location is acceptable.

Once the vent location has been established, please refer to the

appropriate section below for installation details.

Once the vent location has been established, please refer to the

appropriate section below for installation details.

Venting Installation

V+H(MaximumLength)

Max.#

Elbows

100 Feet

6

MultiElbow-VentingInstallation

V1 + H1 + V2 + H2 + V3 = H3

(MaximumLength)

Max.#

Elbows

100 Feet

6

MultiElbow-VentingInstallation

V1 + H1 + D + H2

(MaximumLength)

Max.#

Elbows

40 Feet

6

H

V

Elbow 1

Elbow 2

Elbow 3

Elbow 5

Elbow 4

Elbow 6

H3

H2

H1

V1

V2

V3

H2

H1

V

D

Figure 7 Sec.4 Downward Venting Installations.

Note: PVHIN58-300 cannot be installed closer than 7" feet to fireplace.

R320-ST & R420-ST Power Vent Indoor Gas Fireplace

Page 15

XG0774 - 150121

Installation

PVHIN58-300

Min. 7 feet of pipe between fireplace

and power vent