3.2.2 Thermowell Installation

Standard Thermowell

The most common installation methods are shown below. Consult the factory for

special applications.

3.2.3 Temperature Sensor Installation

The temperature sensor is factory matched and permanently attached to the BTU

MEASUREMENT SYSTEM. Sensors from different Btu meters cannot be used without

being returned to the factory for recalibration.

Apply a thin coat of thermally conductive grease to the temperature sensor, and gently

insert the temperature sensor all the way into the thermowell until it contacts the bottom

of the cavity. Gently tighten the retainer cap. DO NOT OVER TIGHTEN. The thermowell

completely seals the plumbing system without the retainer cap. The only purpose of the

cap is to keep the sensor from losing contact with the bottom of the thermowell cavity.

IMPORTANT NOTE

It is important that no dirt or other foreign material be allowed into the thermowell as this could

affect the thermal response of the system.

CAUTION

Cable length is specified at time of order. This is three wire shielded plenum rated cable.

Altering the cable length will affect calibration. Do not change the cable length without

consulting ONICON.

!