ONICON System-30 MODBUS BTU User Manual

Page 36

Advertising
background image

11451 South Belcher Road, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-30 BTU Measurement System MODBUS RTU RS485 04/14 - 0583-1 / 18345

Page 36

4.8 DIAGNOSTICS

The ONICON System-30 BTU MEASUREMENT

SYSTEM uses a microprocessor to calculate

energy. Factory programmed settings provide

energy total outputs in accordance with the

customer’s application data. An optional

isolated analog output for energy rate, flow rate

or delta T may also be available. Refer to the

Btu meter calibration sheet for a complete listing

of factory settings. These settings cannot be

changed in the field. Contact ONICON factory

service personnel if changes to the calibration

are required.

The System-30 is equipped with diagnostic

indicator lights that confirm the operation of

the microprocessor and its input circuitry.

Please contact the ONICON factory service personnel if either of the diagnostic lights

indicate a potential problem with the operation of the BTU MEASUREMENT SYSTEM.

4.8.1 Diagnostic Lights

Energy

Located on the end of main unit opposite the cable connection is a red LED labeled Btu.

This LED will flash as energy is transferred.

Liquid Flow

Located on the end of main unit opposite the cable connection is a red LED labeled FLOW.

This LED will flash at a rate that is proportional to the liquid flow rate. An unlit LED

indicates no flow signal.

Advertising
This manual is related to the following products: