THERMOWELL INSTALLATION IN WELDED PIPE

3.3 ELECTRICAL INSTALLATION

All user supplied conduit fittings, junction boxes, etc. are to be installed as required by all

applicable building codes.

3.3.1 Single Mode (4 Pipe) Vs. Dual Mode (2 Pipe) Operation

ONICON System 30 BTU Meters may be configured for single or dual mode applications.

Single and dual mode is a reference to the piping system and not the meter itself. Single

mode (4 pipes) applications are those that always have the same relationship between the

supply and return pipe temperatures. In dual mode (2 pipes) applications the polarity of

the temperature differential (Delta t) reverses; often on a seasonal basis.

IMPORTANT NOTE

The System-30-MOD BTU Meter is designed with one internal (Temp1) and one remote (Temp 2)

temperature sensor. If the meter body is located in the supply pipe then the internal temperature

sensor will indicate the supply temperature and the remote sensor will indicate the return

temperature. This relationship will reverse if the meter body is located in the return pipe. The

location of the meter will also affect the logic used to determine mode 1 and mode 2 operations

for dual mode applications. Single mode energy measurements are absolute measurements and

are not effected by polarity of the Delta t.