Sound pressure level – REMKO CMF-120-1P User Manual

Page 53

Advertising
background image

Pump-characteristic curves, indoor module charging pump

Level

Output

in W

Current

in A

I

25

0,12

II

35

0,16

III

45

0,20

Sound pressure level

Level

Output

in W

Current

in A

I

50

0,22

II

55

0,27

III

60

0,30

Pump characteristic curves for models CMF / CMT 120-1P

Pump characteristic curves for models CMF / CMT 160-1P

Distance-dependent sound pressure level for the outdoor unit in relation to installation type, in accordance with the drawing

1m

1m

5m

10m

5m

10m

1m

5m

10m

Distance-dependent sound pressure level

Heat pump

outdoor unit

Sound power level

according to

ISO 9614-2

Installation type,

in accordance

with the drawing

1m

5m

10m

15m

CMF/CMT 120-1P

64,1 dB(A)

In free field

53,1 dB(A) 39,1 dB(A) 33,1 dB(A) 29,6 dB(A)

In front of a wall

56,1 dB(A) 42,1 dB(A) 36,1 dB(A) 32,6 dB(A)

CMF/CMT 160-1P

67,1 dB(A)

In free field

56,1 dB(A) 42,1 dB(A) 36,1 dB(A) 32,6 dB(A)

In front of a wall

59,1 dB(A) 45,1 dB(A) 39,1 dB(A) 35,6 dB(A)