Remko cmf / cmt, Climatic region: -10°c, Climatic region: -12°c – REMKO CMF-120-1P User Manual

Page 56: Climatic region: -14°c, Climatic region: -16°c

Advertising
background image

REMKO CMF / CMT

Climatic region: -10°C

Existing buildings with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF/CMT 120-1P

2,5

3,9

4,4

4,15

4,03

3,82

3,87

3,74

3,60

CMF/CMT 160-1P

2,6

3,9

4,7

4,22

4,09

3,97

3,93

3,80

3,66

New construction with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF/CMT 120-1P

2,5

3,9

4,4

4,07

3,95

3,91

3,78

3,64

3,50

CMF/CMT 160-1P

2,6

3,9

4,7

4,11

3,99

3,86

3,89

3,68

3,54

Climatic region: -12°C

Existing buildings with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF/CMT 120-1P

2,5

3,9

4,4

4,07

3,95

3,82

3,79

3,68

3,53

CMF/CMT 160-1P

2,6

3,9

4,7

4,12

4,00

3,88

3,84

3,71

3,58

New construction with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF/CMT 120-1P

2,5

3,9

4,4

3,98

3,86

3,73

3,69

3,56

3,43

CMF/CMT 160-1P

2,6

3,9

4,7

4,06

3,89

3,81

3,73

3,60

3,46

Climatic region: -14°C

Existing buildings with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF/CMT 120-1P

2,5

3,9

4,4

4,00

3,89

3,77

3,74

3,61

3,49

CMF/CMT 160-1P

2,6

3,9

4,7

4,10

3,98

3,87

3,79

3,67

3,54

New construction with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF/CMT 120-1P

2,5

3,9

4,4

3,92

3,80

3,68

3,64

3,52

3,39

CMF/CMT 160-1P

2,6

3,9

4,7

4,00

3,88

3,75

3,68

3,55

3,42

Climatic region: -16°C

Existing buildings with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF/CMT 120-1P

2,5

3,9

4,4

3,89

3,78

3,67

3,64

3,52

3,39

CMF/CMT 160-1P

2,6

3,9

4,7

3,95

3,84

3,72

3,69

3,57

3,45

New construction with hot-water heating (share 18%)

Type

COP

Annual performance number with inlet/outlet tem-

perature differential: 7K and inlet temperature...

Annual performance number with inlet/outlet tem-

perature differential: 10K and inlet temperature...

A-7/W35

A2/W35

A10/W35

30°C

35°C

40°C

45°C

50°C

55°C

CMF/CMT 120-1P

2,5

3,9

4,4

3,79

3,67

3,56

3,52

3,41

3,28

CMF/CMT 160-1P

2,6

3,9

4,7

3,83

3,72

3,60

3,56

3,45

3,32

Note: A differential of 7K has a standard floor-heating layout, a differential of 10K is typical for a radiator system
Additional key data: a heating-threshold temperature of 15°C for old construction and 12°C in new construction, a differential at the condenser

(test-bench measurements: 5K)

Annual performance number for CMF/CMT 120-1P / CMF/CMT 160-1P

Mode: single energy source, parallel with a switch-over point of -5°C

56