REMKO CMF - DUO

Installation instructions

The indoor unit must be connected
to the two outdoor modules with
refrigerant pipes of dimensions
(outside diameter)

3

/

8

” (approx.

16 mm) and

5

/

8

” (approx. 10 mm).

At least one four-wire control cable

must be laid between the indoor
unit and each of the two outdoor
modules.
Both the indoor unit and outdoor
modules each require a separate

power supply. The power supply
for the indoor unit must not be
permanently switched off in the
event of a block by the energy
supplier

Indoor unit

CMF 320 Duo

Mains cable

Indoor unit

(3x1.5mm

2

)

Condensate drain

(must be designed to be frost proof!)

Control lines

(4x1 mm

2

or standard

5x1.5 mm

2

)

Hot-water supply

and return pipes

(DN 32)

Mains cable

Electric booster

heater (optional)

(5x2.5 mm

2

)

condensate drain

Coolant lines (Cu pipe)
1pc. each

3

/

8

“ and

5

/

8

System Layout CMF 320 Duo

Outdoor unit A

Fan

Outdoor unit B

Fan

Mains supply

400V/3~50Hz 16A

(5x2.5 mm

2

)

Mains supply

400V/3~50Hz 16A

(5x2.5 mm

2

)

Condensate drain

(must be designed to be frost proof!)