Wind

The site for the outdoor
module must be selected
so that machinery noise that
occurs disturbs neither the
residents nor the facility
operator. Observe the TA-

noise specifications as well

as the table containing the

drawings relating to sound

pressure levels on page 45!

NOTE

Assessment level in

accordance with TA

noise

Point of emissions

days

nights

Industrial areas

dB(A)

70

70

Commercial areas

dB(A)

65

50

Core areas, village areas and mixed zones

dB(A)

60

45

General residential areas and small housing estates dB(A)

55

40

Exclusively residential areas

dB(A)

50

35

Spa areas, hospitals and mental institutions

dB(A)

45

35

Isolated noise peaks of short dura-
tion may not exceed 30 dB(A) dur-
ing the day and 20 dB(A) at night.

Snow + 20 cm

j

Positioned side-by-side next to a wall, air outlet open to the front, flow restriction behind

k

Positioned side-by-side next to a wall, air outlet impaired to the front, flow restriction in front and behind

l

Positioned back-to-back; air outlet open to the front























































k

l

j

Minimum distances in mm for the outdoor units and in brackets for the CMF 320 Duo

depending on the enclosure