The following diagram shows the maximum dispensing medium flow rate if the hot water temperature is 45

°C at the dispensing connection, after being mixed with cold water with a temperature of 10 °C. The hot

water temperature set on the controller is 60 °C.

B

[kW]

0

10

20

30

40

50

60

A

[l/min]

0

20

40

60

80

100

120

140

70 °C

90 °C

80 °C

65 °C

Friwa EFS 35

80

90

100

110

120

70

260

280

300

160

180

200

220

240

2

1

Fig. 10: Maximum dispensing medium flow rate

A:

Dispensing medium flow rate [l/min]

B:

Power [kW]

1:

Hot water temperature:

45 °C after heating to 60°C and mixing in cold

water (10 °C)

2:

Buffer storage temperature

Boundary conditions:

Cold water temperature: 10 °C,

Example 1

Hot water temperature on the controller: 60 °C

Temperature in the buffer tank: 70 °C

ð

Maximum dispensing medium flow rate: 53 l/

min, transmission capacity: 129 kW

Example 2

Hot water temperature on the controller: 60 °C

Maximum dispensing medium flow rate: 60 l/min

ð

Temperature in the buffer tank: ~75 °C,

transmission capacity: 155 kW