INSTRUCTIONS FOR PRESSURE TEST GAUGE CONNECTION

Failure to do so may result in death, serious injury or property

damage.

The access panel must be closed tightly during operation.

Never operate the heater with the access panel open or removed.

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE
1.

The installer will provide a 1/8” N.P.T. tapped plug, accessible for test gauge connection immediately

upstream of the gas supply connection to the heater.

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE –

– COMBINATION GAS VALVE IS FACTORY SET

COMBINATION GAS VALVE IS FACTORY SET

COMBINATION GAS VALVE IS FACTORY SET

COMBINATION GAS VALVE IS FACTORY SET

1.

Turn the gas valve to the “OFF” position. Remove the 1/8” plug from the combination gas valve at the Outlet

Outlet

Outlet

Outlet

Pressure T

Pressure T

Pressure T

Pressure Tap

ap

ap

ap shown below and connect a 1/8” nipple to the tapped hole. Connect the test gauge to the

nipple. Turn on the gas supply.

Pressure Regulator Adjustment

(under cap screw)

1/8” NPT

Inlet Pressure

Tap with 3/16” Hex

Allen Wrench Plug

1/8”NPT

Outlet Pressure

Tap with 3/16” Hex

Allen Wrench Plug

Gas Control

Knob

Wiring

Terminals (2)

Ground

Terminals (2)

OUTLET

INLET

CAUTION

Never jumper these terminals. This

shorts out valve coil and may burn

out heat anticipator in thermostat.

STEP-OPENING

GAS CONTROL VALVE

ON

OFF

MV

MV

2.

With the main burner operating, check the burner manifold pressure using a water column manometer.

Gauges that measure pressure in pounds per square inch are not accurate enough to measure or set the
manifold pressure. All measurements MUST BE

MUST BE

MUST BE

MUST BE made when this heater and all other gas burning equipment

that is connected to the gas supply system are operating at maximum capacity.

3.

The combination gas valve is factory set and should not require adjustment.

The combination gas valve is factory set and should not require adjustment.

The combination gas valve is factory set and should not require adjustment.

The combination gas valve is factory set and should not require adjustment. If full rate adjustment is
required, remove the cover screw. Using a small screwdriver, turn the adjustment screw clockwise

to

increase or counterclockwise to decrease the gas pressure to the burner. Replace the cover screw. NOTE:

NOTE:

NOTE:

NOTE:

The step opening pressure of this gas valve is not adjustable.

The step opening pressure of this gas valve is not adjustable.

The step opening pressure of this gas valve is not adjustable.

The step opening pressure of this gas valve is not adjustable.

4.

Check the burner at step pressure, observing burner ignition and flame characteristics. The burner should

ignite properly and without flashback to the orifice, and should remain lit.

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS TYPE

GAS TYPE

GAS TYPE

GAS TYPE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

Minimum*

Minimum*

Minimum*

Minimum*

Maximum

Maximum

Maximum

Maximum

Natural Gas

3.5” W.C.

7” W.C.

14” W.C.

Propane Gas

10.0” W.C.

11” W.C.

14” W.C.

* Minimum permissible gas supply pressure for purpose of input adjustment.