Space Ray RSTP Series User Manual

Page 25

Advertising
background image

Form 43206000

-24-

Sept 2011

Flue vent termination

must be 1 ft. (30cm)

higher than combustion

air inlet cap

Perforated Cover

(Remove)

Control Box

The combustion air inlet should

be not less than 3 ft. (0.9m),

either vertically or horizontally,

from the flue vent termination.

Adapter Plate

Part #42783000

(Install)

End View

6” Starting Collar

(field supplied)

Flue Collar




Combustion Air Cap

(Leslie VersaCap

Type B)

6” Diameter

Single-Wall Pipe

Flashing

1/2” (12mm) fall per 20ft (6m)

toward vent terminal

Horizontal

Through Sidewall

6” (15cm)

Minimum

6” Starting Collar

(field supplied)

3 ft. (91cm)

Minimum

Vertical

Through the roof

Control Box

Perforated Cover

(Remove)

Adapter Plate

Part #42783000

(Install)

End View

Alternate Combustion

Air Intake Location