Rosemount 3051s – Emerson 3051S User Manual

Page 10

Advertising
background image

Quick Installation Guide

00825-0100-4801, Rev HA

February 2008

Rosemount 3051S

10

S

TEP

4

CONTINUED

...

NOTE
Wire colors provided on page 9 are per Belden 3084A DeviceNet
cable. Wire color may vary depending on cable selected.

Belden 3084A DeviceNet cable includes a ground shield. This shield
must be connected to earth ground at either the SuperModule or the
Remote Display, but not both.

Quick Connect Wiring

As standard, the 3051S Quick Connect arrives properly assembled to
the SuperModule and is ready for installation. Cordsets and Field
Wireable Connectors (in shaded area) are sold separately.

Figure 5. Rosemount 3051S Quick Connect Exploded View

IMPORTANT
If Quick Connect is ordered as a 300S spare housing or is removed
from the SuperModule, follow the instructions below for proper
assembly prior to field wiring.

1. Place the Quick Connect onto the SuperModule. To ensure proper

pin alignment, remove coupling nut prior to installing quick connect
onto SuperModule.

Straight Field
Wireable
Connector

(1)(3)

Right Angle Field Wireable
Connector

(2)(3)

Coupling Nut

Cordset

(4)

Quick Connect

Housing

Quick Connect Coupling Nut

(1) Order part number

03151-9063-0001.

(2) Order part number

03151-9063-0002.

(3) Field wiring supplied by customer.
(4) Supplied by cordset vendor.