Quick Installation Guide

00825-0100-4801, Rev HA
February 2008

Rosemount 3051S

11

S

TEP

4

CONTINUED

...

2. Place coupling nut over quick connect and wrench tighten to a

maximum of 300 in-lb. (34 N-m).

3. Tighten the set screw using a

3

/

32

-in hex wrench.

4. Install Cordset/ Field Wireable Connectors onto the Quick Connect.

Do not over tighten.

Figure 6. Quick Connect Housing Pin-Out

Conduit Electrical Connector Wiring (Option GE or GM)

For 3051S transmitters with conduit electrical connectors GE or GM,
refer to the cordset manufacturer’s installation instructions for wiring
details. For FM Intrinsically Safe, non-incendive or FM FISCO
Intrinsically Safe hazardous locations, install in accordance with
Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA 4X
and IP66.) See Appendix B of the 3051S reference manual.

For other wiring

details, refer to pin-out

drawing and the

cordset

manufacturer’s

installation

instructions.

“+”
“–”

Ground

No Connection