Quick Installation Guide

00825-0100-4801, Rev HA
February 2008

Rosemount 3051S

19

NOTES
1. Transmitter output is not safety-rated during the following:
configuration changes, multidrop, loop test. Alternative means should
be used to ensure process safety during transmitter configuration and
maintenance activities.

2. DCS or safety logic solver should be configured to match transmitter
configuration. Figure 9 identifies the three alarm levels available and
their operation values.

Figure 9. Alarm Levels

Rosemount Alarm Level

Namur Alarm Level

Custom Alarm Level

(3)(4)

(1) Transmitter Failure, hardware or software alarm in LO position.

(2) Transmitter Failure, hardware or software alarm in HI position.

(3) High alarm must be at least 0.1 mA higher than the high saturation value.

(4) Low alarm must be at least 0.1 mA lower than the low saturation value.

Normal Operation

4 mA

20 mA

20.8 mA

high saturation

21.75

(2)

3.9 mA

low saturation

3.75 mA

(1)

Normal Operation

4 mA

20 mA

20.5 mA

high saturation

22.5

(2)

3.8 mA

low saturation

3.6 mA

(1)

Normal Operation

4 mA

20 mA

20.1 - 20.5 mA

high saturation

20.2 - 23.0

(2)

3.7 - 3.9 mA

low saturation

3.6 - 3.8 mA

(1)

4801_QIG_RevHA.fm Page 19 Tuesday, February 26, 2008 12:17 PM