Quick Installation Guide

00825-0100-4801, Rev HA

February 2008

Rosemount 3051S

12

S

TEP

4

CONTINUED

...

Power Supply

The dc power supply should provide power with less than two percent
ripple. The total resistance load is the sum of the resistance of the
signal leads and the load resistance of the controller, indicator, and
related pieces. Note that the resistance of intrinsic safety barriers, if
used, must be included.

Figure 7. Load Limitation

Standard Transmitter

HART Diagnostics Transmitter

(option code DA1)

Maximum Loop Resistance =

43.5 * (Power Supply Voltage – 10.5)

Maximum Loop Resistance =

43.5 * (Power Supply Voltage – 12.0)

The HART communicator requires a minimum loop

resistance of 250

Ω for communication.

Voltage (V dc)

Load (Ohms)

Operating

Region

1387

1000

500

0

10.5

20

30

42.4

Voltage (V dc)

Load (Ohms)

Operating

Region

1322

1000

500

0

12.0

20

30

42.4