Quick Installation Guide

00825-0100-4801, Rev HA

February 2008

Rosemount 3051S

30

I7

IECEx Intrinsic Safety
Certificate No.: IECExBAS04.0017X
Ex ia IIC T4 (T

a

= -60 °C to 70 °C)

-HART/Remote Display/Quick Connect/HART Diagnostics
IP66

Conditions for safe use (X)

1. The 3051S HART 4-20mA, 3051S F

OUNDATION

fieldbus,

3051S Profibus and 3051S FISCO are not capable of
withstanding the 500V test as defined in clause 6.4.12 of IEC
60079-11. This must be taken into account during installation.

2. The terminal pins of the Types 3051S-T and 3051S-C must be

protected to IP20 minimum.

N7

IECEx Type n
Certificate No.: IECExBAS04.0018X
Ex nC IIC T4 (Ta = -40 °C to 70 °C)
Ui = 45 Vdc MAX
IP66
Conditions for safe use (X)
The apparatus is not capable of withstanding the 500 V
insulation test required by Clause 8 of IEC 79-15: 1987.

Table 4. Input Parameters

Loop / Power

Groups

U

i

= 30V

All

I

i

= 300 mA

All

P

i

= 1.0W

All

C

i

= 30nF

SuperModule

/Quick Connect

C

i

= 11.4nF

With PlantWeb or Junction Box Housing

C

i

= 0

Remote Display

L

i

= 0

All Except Remote Display

L

i

= 60 µH

Remote Display

4801_QIG_RevHA.fm Page 30 Tuesday, February 26, 2008 12:17 PM