Rosemount 3051S

20

Setting the alarm values and direction is dependent on whether or not
the hardware switch option is installed. You can use a HART master or
communicator to set the Alarm and Saturation values.

Switches installed

1. If using a communicator, use the following fast key sequence to set

the Alarm and Saturation values.
Alarm Levels - Fast Key; 1, 4, 2, 7, 7
Saturation Levels - Fast Key; 1, 4, 2, 7, 8

2. Manually set the direction for the Alarm to HI or LO using the

ALARM switch as shown in Figure 2 on page 6.

Switches not installed

If using a communicator, use the following fast key sequence to set the
Alarm and Saturation values and the Alarm Direction:
Alarm Levels - Fast Key; 1, 4, 2, 7, 7
Saturation Levels - Fast Key; 1, 4, 2, 7, 8
Alarm Direction Fast Key; 1, 4, 2, 7, 6